    商品詳情
      Release date 2012-04-19 13:49 Date of issue 2012-04-19 132960_eng.xml
      KFD2-SR2-Ex2.W
      Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
      Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 1
      Switch Amplifier
      2+
      3-
      1+
      Zone 2
      Div. 2
      Zone 0, 1, 2
      Div. 1, 2
      KFD2-SR2-Ex2.W
      789
      10
      11
      12
      I
      II
      I
      II
      14+ 24 V DC
      15-
      Power Rail
      ERR 24 V DC
      5+
      6-
      4+
      10 kΩ
      10 kΩ
      400 Ω ≤ R ≤ 2 kΩ
      10 kΩ
      10 kΩ
      400 Ω ≤ R ≤ 2 kΩ
      Connection
      Assembly
      • 2-channel isolated barrier
      • 24 V DC supply (Power Rail)
      • Dry contact or NAMUR inputs
      • Relay contact output
      • Line fault detection (LFD)
      • Reversible mode of operation
      • Up to SIL2 acc. to IEC 61508
      Function
      This isolated barrier is used for intrinsic safety applications. It
      transfers digital signals (NAMUR sensors/mechanical
      contacts) from a hazardous area to a safe area.
      The proximity sensor or switch controls a form C changeover
      relay contact for the safe area load. The normal output state
      can be reversed using switches S1 and S2. Switch S3 is used
      to enable or disable line fault detection of the field circuit.
      During an error condition, the relays revert to their deenergized
      state and the LEDs indicate the fault according to
      NAMUR NE44.
      A unique collective error messaging feature is available when
      used with the Power Rail system.
      Features
      1 3
      4 6
      2
      5
      13 15
      12
      9
      10
      7
      14
      11
      8
      KFD2-SR2-Ex2.W
      1
      2
      OUT CHK PWR
      S2
      S1
      S3
      I II
      Front view
      LED yellow:
      Relay output Ι
      LED red:
      LB/SC channel Ι
      LED yellow:
      Relay output ΙΙ
      LED red:
      LB/SC channel ΙΙ
      Switch S3
      (LB/SC-monitoring)
      LED green:
      Power supply
      Removable terminals
      green
      Removable terminals
      blue
      Switch S1
      (Mode of operation channel Ι)
      Switch S2
      (Mode of operation channel ΙΙ)
      2
      Release date 2012-04-19 13:49 Date of issue 2012-04-19 132960_eng.xml
      Technical data KFD2-SR2-Ex2.W
      Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
      Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 2
      General specifications
      Signal type Digital Input
      Supply
      Connection Power Rail or terminals 14+, 15-
      Rated voltage 20 ... 30 V DC
      Ripple ≤ 10 %
      Rated current ≤ 50 mA
      Power loss 1 W
      Power consumption < 1.3 W
      Input
      Connection terminals 1+, 2+, 3-; 4+, 5+, 6-
      Rated values acc. to EN 60947-5-6 (NAMUR)
      Open circuit voltage/short-circuit current approx. 8 V DC / approx. 8 mA
      Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
      Line fault detection breakage I ≤ 0.1 mA , short-circuit I > 6 mA
      Pulse/Pause ratio ≥ 20 ms / ≥ 20 ms
      Output
      Connection output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12
      Output I, II signal, relay
      Minimum switch current 2 mA / 24 V DC
      Energized/De-energized delay approx. 20 ms / approx. 20 ms
      Mechanical life 107 switching cycles
      Transfer characteristics
      Switching frequency ≤ 10 Hz
      Electrical isolation
      Output/power supply reinforced insulation according to IEC 61140, rated insulation voltage 300 Veff
      Output/Output reinforced insulation according to IEC 61140, rated insulation voltage 300 Veff
      Directive conformity
      Electromagnetic compatibility
      Directive 2004/108/EC EN 61326-1:2006
      Low voltage
      Directive 2006/95/EC EN 61010-1:2010
      Conformity
      Electromagnetic compatibility NE 21
      Protection degree IEC 60529
      Protection against electric shock IEC 61140
      Ambient conditions
      Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
      Mechanical specifications
      Protection degree IP20
      Mass approx. 150 g
      Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2
      Mounting on 35 mm DIN mounting rail acc. to DIN EN 60715
      Data for application in connection
      with Ex-areas
      EC-Type Examination Certificate PTB 00 ATEX 2080 , for additional certificates see www.pepperl-fuchs.com
      Group, category, type of protection ¬ II (1) G [Ex ia] IIC, II (1) D [Ex ia] IIIC
      Input [Ex ia] IIC, [Ex ia] IIIC
      Voltage Uo 10.5 V
      Current Io 13 mA
      Power Po 34 mW (linear characteristic)
      Supply
      Maximum safe voltage Um 253 V AC / 125 V DC (Attention! Um is no rated voltage.)
      Output
      Contact loading 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
      Maximum safe voltage Um 253 V AC (Attention! The rated voltage can be lower.)
      Statement of conformity Pepperl+Fuchs
      Group, category, type of protection ¬ II (3)G [Ex ic] IIC; [Ex nL] IIC
      Input [Ex ic] IIC; [Ex nL] IIC
      Voltage Uo 10.5 V
      Current Io 13 mA
      Power Po 34 mW (linear characteristic)
      Output
      Contact loading 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
      Release date 2012-04-19 13:49 Date of issue 2012-04-19 132960_eng.xml
      Technical data KFD2-SR2-Ex2.W
      Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
      Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 3
      Statement of conformity TÜV 99 ATEX 1493 X , observe statement of conformity
      Group, category, type of protection,
      temperature class
      ¬ II 3G Ex nA nC IIC T4
      Output
      Contact loading 50 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
      Electrical isolation
      Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
      Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
      Directive conformity
      Directive 94/9/EC EN 60079-0:2009, EN 60079-11:2007 , EN 60079-15:2005 , EN 61241-11:2006
      International approvals
      FM approval
      Control drawing 116-0035
      CSA approval
      Control drawing 116-0047
      IECEx approval IECEx PTB 11.0034
      Approved for [Ex ia] IIC , [Ex ia] IIIC , [Ex ia] I
      General information
      Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of
      Conformity and instructions have to be observed where applicable. For information see www.pepperlfuchs.
      com.
      Release date 2012-04-19 13:49 Date of issue 2012-04-19 132960_eng.xml
      Technical data KFD2-SR2-Ex2.W
      Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
      Pepperl+Fuchs Group • Tel.: Germany +49-621-776-0 • USA +1-330-4253555 • Singapore +65-67-799091 • Internet www.pepperl-fuchs.com 4
      Power feed module KFD2-EB2
      The power feed module is used to supply the devices with 24 V DC via the Power Rail. The fuse-protected power feed module
      can supply up to 150 individual devices depending on the power consumption of the devices. A galvanically isolated mechanical
      contact uses the Power Rail to transmit collective error messages.
      Power Rail UPR-03
      The Power Rail UPR-03 is a complete unit consisting of the electrical inset and an aluminium profile rail 35 mm x 15 mm. To make
      electrical contact, the devices are simply engaged.
      Profile Rail K-DUCT with Power Rail
      The profile rail K-DUCT is an aluminum profile rail with Power Rail insert and two integral cable ducts for system and field cables.
      Due to this assembly no additional cable guides are necessary.
      Power Rail and Profile Rail must not be fed via the device terminals of the individual devices!
      Configuration
      7 8 9
      10 11 12
      1 2 3
      4 5 6
      13 14 15
      1
      2
      OUT CHK PWR
      S1
      S2
      S3
      1 2 3
      1 2 3
      S1
      S3
      II
      S2
      I
      Switch position
      Operating status
      Factory settings: switch 1, 2 and 3 in position I
      S Function Position
      1 Mode of operation
      Output I (relay)
      energized
      with high input current I
      with low input current II
      2 Mode of operation
      Output II (relay)
      energized
      with high input current I
      with low input current II
      3 Line fault detection ON I
      OFF II
      Control circuit Input signal
      Initiator high impedance/
      contact opened
      low input current
      Initiator low impedance/
      contact closed
      high input current
      Lead breakage,
      lead short-circuit
      Line fault
      Accessories
    在線詢盤/留言
  • 0571-87774297  
    主站蜘蛛池模板: 亚洲福利视频一区| 国产精品亚洲欧美大片在线观看| 亚洲成a人片在线看| 药店打针1_标清| 国产高清一级伦理| 久99频这里只精品23热视频| 欧美日韩亚洲另类| 可播放的gαy片男男| 日韩视频第二页| 天天躁日日躁狠狠躁欧美老妇 | 欧美人与物另类| 女人国产香蕉久久精品| 久久精品国产99国产精品亚洲 | 青苹果乐园影视免费观看电视剧hd| 国内精品久久久久久影院| 久久嫩草影院免费看夜色| 永久免费无内鬼放心开车| 啊灬用力灬啊灬啊灬啊| 亚洲娇小性xxxx| 天天躁狠狠躁夜躁2021| 久久久亚洲欧洲日产国码农村| 欧美日韩大片在线观看| 午夜成人理论福利片| 国产精品三级视频| 国外bbw免费视频| 中文人妻熟妇乱又伦精品| 最近中文字幕免费完整| 亚洲黄色片免费看| 美女污污视频网站| 国产成人精品福利网站在线观看 | 强行被公侵犯奈奈美| 久久精品免费大片国产大片| 欧美视频一区在线观看| 十九岁日本电影免费完整版观看| 黄色一级毛片看一级毛片| 国产老买老妇bbb| www久久精品| 无码人妻精品一区二区| 亚洲av永久无码精品网站| 波多野结衣导航| 北条麻妃一区二区三区av高清|